Specifications
Model: RCF151 / RCF152
Rated Voltage:
-
RCF151: AC100V (85–110%)
-
RCF152: AC200V (85–110%)
Frequency: 50/60Hz
Power Consumption: 7VA
Contact Capacity of Devices:
-
Terminal ① (Main Valve): 100VA
-
Terminal ⑤ (Pilot Valve): 100VA
-
Terminal ⑨ (Ignition Transformer): 250VA
-
Terminal ⑧ (Alarm): 75VA
Allowable Ambient Temperature: -20°C to +60°C
Allowable Ambient Humidity: 35% – 90% RH (at ambient temperature of 40°C)
Withstand Voltage:
-
Between each terminal (excluding ④ & ⑥) and ground: AC1500V for 1 min or AC1800V for 1s
Insulation Resistance: -
50 MΩ or more (with DC500V Megger)
Lightning Surge Immunity: 3kV 1.2/50μs (IEC61000-4-5)
Mounting Direction: Reset button faces upwards or sideways
Mass: Approx. 395g
Application
For gas-fired combustion equipment with a combustion rate up to 175 kW/h or less (batch operation type).
Flame Detector Type: Flame Rod Detector
Sequence Timing
-
Pre-purge: 15 ±1 sec
-
Ignition Trial: 4 ±1 sec
-
Post-ignition: 1 ±1 sec
-
Lockout: 15 ±1 sec
-
Flame Response: 1 sec
Flame Current
-
Normal Combustion: 2–6μA (between flame rod and terminal ④)
-
Detection Threshold:
-
Flame: Maximum 1.0μA
-
Non-flame: Minimum 0.2μA
-
Key Differences Between RCF151 and RCF152:
Feature | RCF151 | RCF152 |
---|---|---|
Rated Voltage | AC100V | AC200V |
Application Power | Lower voltage setups | Higher voltage setups |
Other Specs | Identical to RCF152 | Identical to RCF151 |
Both models offer the same control logic, safety features, and operation sequences—only the rated voltage differs, allowing users to select based on their specific electrical setup.